Артикул: AF185-30-22-70

Артикул: AF185-30-22-70

AF185-30-22 100-250V 50/60Hz / 100-250V DC Contactor
Мы подберем для вас подходящий продукт
sales@industry-analytics.ru
+7 (926) 540-72-98
Срочная доставка
Параллельный импорт

Конфигурация



























































General Information
Extended Product Type: AF185-30-22-70
Product ID: 1SFL497001R7022
EAN: 7320500222713
Catalog Description: AF185-30-22 100-250V 50/60Hz / 100-250V DC Contactor
Long Description: A 3-phase Contactor suitable for various applications such as Motor starting, Isolation, By-pass and Distribution application up to max 1000 V. Operated with wide control voltage range 100-250 V, AC/DC

Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85364900
Replacement Product ID (NEW): 1SFL487002R1322
Popular Downloads
Data Sheet, Technical Information: 1SBC100192C0206
Instructions and Manuals: 1SFC380003-89
Dimension Diagram: 53540923-7

Dimensions
Product Net Width: 123.5 mm
Product Net Depth / Length: 160 mm
Product Net Height: 196 mm
Product Net Weight: 2.9 kg

Technical
Number of Main Contacts NO: 3
Number of Main Contacts NC: 0
Number of Auxiliary Contacts NO: 2
Number of Auxiliary Contacts NC: 2
Rated Operational Voltage: Main Circuit 690 V
Rated Frequency (f): Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith): acc. to IEC 60947-4-1, Open Contactors q = 40 °C 275 A
Rated Operational Current AC-1 (Ie): (1000 V) 40 °C 200 A
(1000 V) 55 °C 200 A
(1000 V) 70 °C 180 A
(690 V) 40 °C 275
(690 V) 55 °C 250
(690 V) 70 °C 180
Rated Operational Current AC-3 (Ie): (415 V) 55 °C 185 A
(440 V) 55 °C 185 A
(500 V) 55 °C 170 A
(690 V) 55 °C 170 A
(1000 V) 55 °C 95 A
(380 / 400 V) 55 °C 185 A
(220 / 230 / 240 V) 55 °C 185
Rated Operational Power AC-3 (Pe): (415 V) 90 kW
(440 V) 90 kW
(500 V) 110 kW
(690 V) 132 kW
(1000 V) 132 kW
(380 / 400 V) 90 kW
(220 / 230 / 240 V) 55 kW
Rated Breaking Capacity AC-3 acc. to IEC 60947-4-1: 8 x Ie AC-3
Rated Making Capacity AC-3 acc. to IEC 60947-4-1: 10 x Ie AC-3
Short-Circuit Protective Devices: gG Type Fuses 355 A
Rated Short-time Withstand Current (Icw): at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1500 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 320 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 800 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 2000 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 1000 A
Maximum Breaking Capacity: cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 2000 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 1600 A
Maximum Electrical Switching Frequency: (AC-1) 300 cycles per hour
(AC-2 / AC-4) 150 cycles per hour
(AC-3) 300 cycles per hour
Rated Operational Current DC-1 (Ie): (110 V) 2 Poles in Series, 40 °C 275 A
(220 V) 3 Poles in Series, 40 °C 275 A
Rated Operational Current DC-3 (Ie): (110 V) 2 Poles in Series, 40 °C 275 A
(220 V) 3 Poles in Series, 40 °C 275 A
Rated Operational Current DC-5 (Ie): (110 V) 2 Poles in Series, 40 °C 275 A
(220 V) 3 Poles in Series, 40 °C 275 A
Rated Insulation Voltage (Ui): acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp): Main Circuit 8 kV
Mechanical Durability: 5 million
Maximum Mechanical Switching Frequency: 300 cycles per hour
Coil Operating Limits: (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Rated Control Circuit Voltage (Uc): 50 Hz 100 ... 250 V
60 Hz 100 ... 250 V
DC Operation 100 ... 250 V
Coil Consumption: Holding at Max. Rated Control Circuit Voltage 50 Hz 12 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 12 V·A
Holding at Max. Rated Control Circuit Voltage DC 2 W
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 430 V·A
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 430 V·A
Pull-in at Max. Rated Control Circuit Voltage DC 500 W
Operate Time: Between Coil De-energization and NC Contact Closing 40 .... 50 ms
Between Coil De-energization and NO Contact Opening 43 ... 53 ms
Between Coil Energization and NC Contact Opening 45 ... 85 ms
Between Coil Energization and NO Contact Closing 50 ... 90 ms
Connecting Capacity Main Circuit: Bar 24 mm²
Rigid Al-Cable 25 ... 150 mm²
Rigid Cu-Cable 6 ... 185 mm²
Connecting Capacity Auxiliary Circuit: Flexible with Ferrule 2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²
Flexible 1x0.75 ... 2.5 mm²
Solid 2 x 1 ... 4 mm²
Stranded 2 x 1 .... 4 mm²
Degree of Protection: acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Terminal Type: Main Circuit: Bars
Technical UL/CSA
Maximum Operating Voltage UL/CSA: Main Circuit 600 V
General Use Rating UL/CSA: (600 V AC) 250 A
Horsepower Rating UL/CSA: (200 V AC) Three Phase 50 hp
(208 V AC) Three Phase 50 hp
(220 ... 240 V AC) Three Phase 60 hp
(440 ... 480 V AC) Three Phase 125 hp
(550 ... 600 V AC) Three Phase 150 hp

Environmental
Ambient Air Temperature: Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... +50 °C
Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... +70 °C
Close to Contactor for Storage -40 ... +70 °C
Maximum Operating Altitude Permissible: 3000 m
Resistance to Shock acc. to IEC 60068-2-27: Shock Direction: A 5 K40
Shock Direction: B1 5 K40
Shock Direction: B2 5 K40
Shock Direction: C1 5 K40
Shock Direction: C2 5 K40
RoHS Status: Following EU Directive 2011/65/EU

Certificates and Declarations (Document Number)
ABS Certificate: 15-LD1408622-PDA
BV Certificate: BV_13409-C0BV
CB Certificate: SEMKO_SE-69479
CCS Certificate: GB14T00030
CQC Certificate: CQC2007010304256685
CQC2009010304353527
cUL Certificate: 20160920-E36588
Declaration of Conformity - CCC: 2020980304001634
2020980304001069
Declaration of Conformity - CE: 2CMT2015-005436
DNV GL Certificate: TAE00001W1
EAC Certificate: 9AKK107046A8618
Environmental Information: 1SFC101007D0201
GL Certificate: GL_20261-04HH
Instructions and Manuals: 1SFC380003-89
LOVAG Certificate: SE-0115106
LR Certificate: 16-20064
RINA Certificate: ELE060313XG_002
RMRS Certificate: RMRS_12-03683-315
RoHS Information: 2CMT2015-005436

Container Information
Package Level 1 Units: box 1 piece
Package Level 1 Width: 178 mm
Package Level 1 Depth / Length: 232 mm
Package Level 1 Height: 167 mm
Package Level 1 Gross Weight: 3.5 kg
Package Level 1 EAN: 7320500222713

Classifications
Object Classification Code: Q
ETIM 4: EC000066 - Magnet contactor, AC-switching
ETIM 5: EC000066 - Magnet contactor, AC-switching
ETIM 6: EC000066 - Power contactor, AC switching
ETIM 7: EC000066 - Power contactor, AC switching
eClass: V11.0 : 27371003
UNSPSC: 39121529
IDEA Granular Category Code (IGCC): 4755 >> Contactors