Артикул: AE50-30-11 125V DC
Артикул: AE50-30-11 125V DC
AE50-30-11 125V DC Contactor
Мы подберем для вас подходящий продукт
Срочная доставка
Параллельный импорт
Конфигурация
General Information | |
Extended Product Type: | AE50-30-11 125V DC |
Product ID: | 1SBL359001R8711 |
EAN: | 3471522104878 |
Catalog Description: | AE50-30-11 125V DC Contactor |
Long Description: | AE50 contactors are mainly used for controlling 3-phase motors and generally for controlling power circuits up to 690 V AC / 1000 V AC or 220 V DC. The contactors can also be used for many other applications such as isolation, capacitor switching, lighting. The AE... series 1-stack 3-pole contactors are of the block type design. - Main poles and auxiliary contact blocks: 3 main poles and 2 built-in auxiliary contacts, front-mounted add-on auxiliary contact blocks - Control circuit: DC operated with standard double-winding DC coils (with add-on factory-mounted lagging contact for insertion of the"holding" winding) - Accessories: a wide range of accessories is available. |
| |
Minimum Order Quantity: | 1 piece |
Customs Tariff Number: | 85364900 |
Popular Downloads | |
Data Sheet, Technical Information: | 1SBC100122C0202_Ch02 |
Instructions and Manuals: | FPTC407700P0003 |
| |
Product Net Width: | 94 mm |
Product Net Depth / Length: | 108 mm |
Product Net Height: | 110 mm |
Product Net Weight: | 1.24 kg |
| |
Number of Main Contacts NO: | 3 |
Number of Main Contacts NC: | 0 |
Number of Auxiliary Contacts NO: | 1 |
Number of Auxiliary Contacts NC: | 1 |
Standards: | Devices complying with international standards IEC 947-1 / 947-4-1 and European standards EN 60 947-1 / 60 947-4-1. Electromagnetic compatibility (EMC) according to amendment A11 to IEC 947-1, EN 60 947-1 and amendment 2 to IEC 947-4-1 |
Rated Operational Voltage: | Main Circuit 1000 V |
Rated Frequency (f): | Supply Circuit 50 / 60 Hz |
Conventional Free-air Thermal Current (Ith): | acc. to IEC 60947-4-1, Open Contactors q = 40 °C 100 A |
acc. to IEC 60947-5-1, q = 40 °C 16 A | |
Rated Operational Current AC-1 (Ie): | (690 V) 40 °C 100 |
(690 V) 55 °C 85 | |
(690 V) 70 °C 70 | |
Rated Operational Current AC-3 (Ie): | (415 V) 55 °C 50 A |
(440 V) 55 °C 45 A | |
(500 V) 55 °C 45 A | |
(690 V) 55 °C 35 A | |
(1000 V) 55 °C 23 A | |
(380 / 400 V) 55 °C 50 A | |
(220 / 230 / 240 V) 55 °C 53 | |
Rated Operational Power AC-3 (Pe): | (415 V) 25 kW |
(440 V) 25 kW | |
(500 V) 30 kW | |
(690 V) 30 kW | |
(380 / 400 V) 22 kW | |
(220 / 230 / 240 V) 15 kW | |
Rated Breaking Capacity AC-3 acc. to IEC 60947-4-1: | 8 x Ie AC-3 |
Rated Making Capacity AC-3 acc. to IEC 60947-4-1: | 10 x Ie AC-3 |
Rated Operational Current AC-15 (Ie): | (500 V) 2 A |
(690 V) 2 A | |
(24 / 127 V) 6 A | |
(220 / 240 V) 4 A | |
(380 / 400 V) 3 A | |
Short-Circuit Protective Devices: | Auxiliary Circuit - gG Type Fuses 10 A |
gG Type Fuses 100 A | |
Maximum Breaking Capacity: | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1300 A |
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 630 A | |
Maximum Electrical Switching Frequency: | (AC-1) 300 cycles per hour |
(AC-2 / AC-4) 150 cycles per hour | |
(AC-3) 300 cycles per hour | |
Rated Operational Current DC-13 (Ie): | (24 V) 6 / 144 A |
(48 V) 2.8 / 134 A | |
(72 V) 1 / 72 A | |
(125 V) 0.55 / 69 A | |
(250 V) 0.3 / 75 A | |
Rated Insulation Voltage (Ui): | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V |
acc. to IEC 60947-5-1 and VDE 0110 (Gr. C) 690 V | |
acc. to UL/CSA 600 V | |
Rated Impulse Withstand Voltage (Uimp): | 8 kV |
Mechanical Durability: | 5 million |
Maximum Mechanical Switching Frequency: | 3600 cycles per hour |
Rated Control Circuit Voltage (Uc): | DC Operation 125 V |
Coil Consumption: | Average Holding Value, from Warm State 4 W |
Average Pull-in Value, from Cold State 200 W | |
Pull-in at Max. Rated Control Circuit Voltage DC 200 W | |
Operate Time: | Between Coil De-energization and NC Contact Closing 8 ... 18 ms |
Between Coil De-energization and NO Contact Opening 5 ... 15 ms | |
Between Coil Energization and NC Contact Opening 10 ... 27 ms | |
Between Coil Energization and NO Contact Closing 30 ... 30 ms | |
Connecting Capacity Main Circuit: | Flexible with Cable End 6 ... 16 mm² |
Rigid Cable 6 ... 25 mm² | |
Connecting Capacity Auxiliary Circuit: | Flexible with Cable End 0.75 ... 2.5 mm² |
Rigid Cable 1 ... 4 mm² | |
Degree of Protection: | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP40 |
Connecting Terminals (delivered in open position) Main Poles: | M 6 (+,-) pozidriv 2 screws with 1x (13 x 10 mm) connector |
Terminal Type: | Screw Terminals |
| |
Ambient Air Temperature: | Close to Contactor Fitted with Thermal O/L Relay -25 ... +55 °C |
Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... +55 °C | |
Close to Contactor without Thermal O/L Relay (Uc) -40 ... +70 °C | |
Close to Contactor for Storage -60 ... +80 °C | |
Climatic Withstand: | acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II |
Maximum Operating Altitude Permissible: | 3000 m |
RoHS Status: | Following EU Directive 2011/65/EU |
| |
ASEFA Certificate: | ASEFA_10801-10901 |
CB Certificate: | CB_CN45323 |
CCC Certificate: | CCC_2018010304129269 |
CQC Certificate: | CQC2018010304129269 |
CSA Certificate: | CSA_1033838_LR056745 |
Declaration of Conformity - CCC: | 2020980304001621 |
Declaration of Conformity - CE: | 1SBD250804U1000 |
EAC Certificate: | EAC_RU C-FR ME77 B01010 |
Environmental Information: | 1SBD250017E1003 |
GOST Certificate: | GOST_POCCFRME77B07175 |
Instructions and Manuals: | FPTC407700P0003 |
LOVAG Certificate: | LOVAG_FR01002 |
RMRS Certificate: | RMRS_0507015250 |
RoHS Information: | 1SBD250804U1000 |
UL Certificate: | UL_20120830-E312527-10-1 |
UL Listing Card: | UL_E312527 |
| |
Package Level 1 Units: | 1 piece |
Package Level 1 Width: | 140 mm |
Package Level 1 Depth / Length: | 146 mm |
Package Level 1 Height: | 96 mm |
Package Level 1 Gross Weight: | 1.24 kg |
Package Level 1 EAN: | 3471522104878 |
Package Level 2 Units: | box 20 piece |
Package Level 2 Width: | 503 mm |
Package Level 2 Depth / Length: | 153 mm |
Package Level 2 Height: | 307 mm |
Package Level 2 Gross Weight: | 24.8 kg |
Package Level 3 Units: | 160 piece |
| |
Object Classification Code: | Q |
ETIM 4: | EC000066 - Magnet contactor, AC-switching |
ETIM 5: | EC000066 - Magnet contactor, AC-switching |
ETIM 6: | EC000066 - Power contactor, AC switching |
ETIM 7: | EC000066 - Power contactor, AC switching |
eClass: | V11.0 : 27371018 |
UNSPSC: | 39121529 |