Артикул: AF750-30-22-68
Мы подберем для вас подходящий продукт
Срочная доставка
Параллельный импорт
Конфигурация
General Information | |
Extended Product Type: | AF750-30-22-68 |
Product ID: | 1SFL637001R6822 |
EAN: | 7320500222058 |
Catalog Description: | AF750-30-22 24-60V DC Contactor |
Long Description: | The AF750-30-22-68 is a 3 pole - 1000 V IEC or 600 V UL contactor with pre-mounted auxiliary contacts and Main Circuit Bars, controlling motors up to 400 kW / 400 V AC (AC-3) or 600 hp / 480 V UL and switching power circuits up to 1050 A (AC-1) or 900 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (24-60 V DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories. |
| |
Minimum Order Quantity: | 1 piece |
Customs Tariff Number: | 85364900 |
Popular Downloads | |
Data Sheet, Technical Information: | 1SBC100192C0206 |
Instructions and Manuals: | 1SFC380023-en |
Dimension Diagram: | 53540919-60 |
| |
Product Net Width: | 210 mm |
Product Net Depth / Length: | 242 mm |
Product Net Height: | 283 mm |
Product Net Weight: | 13.6 kg |
| |
Number of Main Contacts NO: | 3 |
Number of Main Contacts NC: | 0 |
Number of Auxiliary Contacts NO: | 2 |
Number of Auxiliary Contacts NC: | 2 |
Rated Operational Voltage: | Main Circuit 1000 V |
Rated Frequency (f): | Main Circuit 50 / 60 Hz |
Conventional Free-air Thermal Current (Ith): | acc. to IEC 60947-4-1, Open Contactors q = 40 °C 1050 A |
Rated Operational Current AC-1 (Ie): | (1000 V) 40 °C 1000 A |
(1000 V) 55 °C 875 A | |
(1000 V) 70 °C 720 A | |
(690 V) 40 °C 1050 | |
(690 V) 55 °C 875 | |
(690 V) 70 °C 720 | |
Rated Operational Current AC-3 (Ie): | (415 V) 55 °C 750 A |
(440 V) 55 °C 750 A | |
(500 V) 55 °C 750 A | |
(690 V) 55 °C 650 A | |
(1000 V) 55 °C 300 A | |
(380 / 400 V) 55 °C 750 A | |
(220 / 230 / 240 V) 55 °C 750 | |
Rated Operational Power AC-3 (Pe): | (415 V) 425 kW |
(440 V) 450 kW | |
(500 V) 520 kW | |
(690 V) 600 kW | |
(1000 V) 400 kW | |
(380 / 400 V) 400 kW | |
(220 / 230 / 240 V) 220 kW | |
Rated Breaking Capacity AC-3 acc. to IEC 60947-4-1: | 8 x Ie AC-3 |
Rated Making Capacity AC-3 acc. to IEC 60947-4-1: | 10 x Ie AC-3 |
Short-Circuit Protective Devices: | gG Type Fuses 1000 A |
Rated Short-time Withstand Current (Icw): | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 6400 A |
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 1300 A | |
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 3500 A | |
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 7000 A | |
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 4500 A | |
Maximum Breaking Capacity: | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 7500 A |
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 7000 A | |
Maximum Electrical Switching Frequency: | (AC-1) 300 cycles per hour |
(AC-2 / AC-4) 60 cycles per hour | |
(AC-3) 300 cycles per hour | |
Rated Operational Current DC-1 (Ie): | (110 V) 1-Pole, 40 °C 1050 A |
(110 V) 2 Poles in Series, 40 °C 1050 A | |
(220 V) 3 Poles in Series, 40 °C 1050 A | |
(600 V) 3 Poles in Series, 40 °C 1050 A | |
(850 V) 3 Poles in Series, 40 °C 1050 A | |
Rated Operational Current DC-3 (Ie): | (110 V) 1-Pole, 40 °C 1050 A |
(110 V) 2 Poles in Series, 40 °C 1050 A | |
(220 V) 3 Poles in Series, 40 °C 1050 A | |
(600 V) 3 Poles in Series, 40 °C 1050 A | |
(850 V) 3 Poles in Series, 40 °C 1050 A | |
Rated Operational Current DC-5 (Ie): | (110 V) 1-Pole, 40 °C 1050 A |
(110 V) 2 Poles in Series, 40 °C 1050 A | |
(220 V) 3 Poles in Series, 40 °C 1050 A | |
(600 V) 3 Poles in Series, 40 °C 1050 A | |
(850 V) 3 Poles in Series, 40 °C 1050 A | |
Rated Insulation Voltage (Ui): | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V |
acc. to UL/CSA 600 V | |
Rated Impulse Withstand Voltage (Uimp): | Main Circuit 8 kV |
Mechanical Durability: | 3 million |
Maximum Mechanical Switching Frequency: | 300 cycles per hour |
Coil Operating Limits: | (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C) |
Rated Control Circuit Voltage (Uc): | DC Operation 24 ... 60 V |
Coil Consumption: | Holding at Max. Rated Control Circuit Voltage 50 Hz 12 V·A |
Holding at Max. Rated Control Circuit Voltage 60 Hz 12 V·A | |
Holding at Max. Rated Control Circuit Voltage DC 5.5 V·A | |
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 780 V·A | |
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 780 V·A | |
Pull-in at Max. Rated Control Circuit Voltage DC 785 V·A | |
Operate Time: | Between Coil De-energization and NC Contact Closing 50 ... 70 ms |
Between Coil De-energization and NO Contact Opening 53 ... 73 ms | |
Between Coil Energization and NC Contact Opening 45 ... 115 ms | |
Between Coil Energization and NO Contact Closing 50 ... 120 ms | |
Connecting Capacity Main Circuit: | Bar 52 mm² |
Rigid Al-Cable 300 mm² | |
Rigid Cu-Cable 300 mm² | |
Connecting Capacity Auxiliary Circuit: | Flexible with Ferrule 2x 0.75 ... 2.5 mm² |
Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm² | |
Flexible 1x0.75 ... 2.5 mm² | |
Solid 2 x 1 ... 4 mm² | |
Stranded 2 x 1 .... 4 mm² | |
Degree of Protection: | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 |
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00 | |
Terminal Type: | Main Circuit: Bars |
Technical UL/CSA | |
Maximum Operating Voltage UL/CSA: | Main Circuit 1000 V |
General Use Rating UL/CSA: | (1000 V AC) 900 A |
(600 V AC) 900 A | |
Horsepower Rating UL/CSA: | (200 V AC) Three Phase 250 hp |
(208 V AC) Three Phase 250 hp | |
(220 ... 240 V AC) Three Phase 300 hp | |
(440 ... 480 V AC) Three Phase 600 hp | |
(550 ... 600 V AC) Three Phase 700 hp | |
| |
Ambient Air Temperature: | Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... +50 °C |
Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... +70 °C | |
Close to Contactor for Storage -40 ... +70 °C | |
Maximum Operating Altitude Permissible: | 3000 m |
Resistance to Shock acc. to IEC 60068-2-27: | Shock Direction: A 5 K40 |
Shock Direction: B1 5 K40 | |
Shock Direction: B2 5 K40 | |
Shock Direction: C1 5 K40 | |
Shock Direction: C2 5 K40 | |
RoHS Status: | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| |
ABS Certificate: | 15-LD1408622-PDA |
BV Certificate: | BV_13409-C0BV |
CB Certificate: | SE-82863 |
CCS Certificate: | GB14T00030 |
CQC Certificate: | CQC2007010304256684 |
CQC2012010304540080 | |
CSA Certificate: | 306712-1 |
cUL Certificate: | UL_20111101-E36588 |
Declaration of Conformity - CCC: | 2020980304001301 |
2020980304001045 | |
Declaration of Conformity - CE: | 2CMT2019-005796 |
DNV Certificate: | DNV_E-10966 |
DNV GL Certificate: | TAE00001W1 |
EAC Certificate: | 9AKK107046A8618 |
Environmental Information: | 1SFC101005D0201 |
1SAC200044H0006 | |
GL Certificate: | GL_42988-02HH |
Instructions and Manuals: | 1SFC380023-en |
LOVAG Certificate: | SE-0151293 |
LR Certificate: | 16-20064 |
PRS Certificate: | TE_2092_880423_16 |
RINA Certificate: | ELE060313XG_002 |
RMRS Certificate: | 9AKK107045A6978 |
RoHS Information: | 2CMT2019-005796 |
UL Listing Card: | UL_E36588 |
| |
Package Level 1 Units: | box 1 piece |
Package Level 1 Width: | 280 mm |
Package Level 1 Depth / Length: | 375 mm |
Package Level 1 Height: | 310 mm |
Package Level 1 Gross Weight: | 15 kg |
Package Level 1 EAN: | 7320500222058 |
| |
Object Classification Code: | Q |
ETIM 4: | EC000066 - Magnet contactor, AC-switching |
ETIM 5: | EC000066 - Magnet contactor, AC-switching |
ETIM 6: | EC000066 - Power contactor, AC switching |
ETIM 7: | EC000066 - Power contactor, AC switching |
eClass: | V11.0 : 27371003 |
UNSPSC: | 39121529 |
IDEA Granular Category Code (IGCC): | 4755 >> Contactors |