Артикул: AFC30-30-00K-81

Артикул: AFC30-30-00K-81

AFC30-30-00K-81 24V 50/60Hz Contactor
Мы подберем для вас подходящий продукт
sales@industry-analytics.ru
+7 (926) 540-72-98
Срочная доставка
Параллельный импорт

Конфигурация















































General Information
Extended Product Type: AFC30-30-00K-81
Product ID: 1SBL271005R8100
EAN: 3471523015005
Catalog Description: AFC30-30-00K-81 24V 50/60Hz Contactor
Long Description: The AFC30-30-00K-81 is a 3 poles - 690 V IEC or 600V UL contactor with Push-In terminals, controlling motors up to 15 kW / 400 V AC (AC-3) or 20 hp / 480 V AC UL and switching power circuits up to 50 A (AC-1) or 45 A UL general use. Within the AF platform, AFC contactors offer an optimized operating time for AC controlled applications with electromagnetic coil (control voltage : 24 V AC 50/60 Hz). AFC contactors have a block type design and can be easily extended with add-on auxiliary contact blocks and a wide range of additionnal accessories.

Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85364900
Popular Downloads
Instructions and Manuals: 1SBC101060M6801

Dimensions
Product Net Width: 45 mm
Product Net Depth / Length: 86 mm
Product Net Height: 92.3 mm
Product Net Weight: 0.359 kg

Technical
Number of Main Contacts NO: 3
Number of Main Contacts NC: 0
Number of Auxiliary Contacts NO: 0
Number of Auxiliary Contacts NC: 0
Standards: IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1, UL 508, CSA C22.2 N°14
Rated Operational Voltage: Main Circuit 690 V
Rated Frequency (f): Auxiliary Circuit 50 / 60 Hz
Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith): acc. to IEC 60947-4-1, Open Contactors q = 40 °C 50 A
acc. to IEC 60947-5-1, q = 40 °C 16 A
Rated Operational Current AC-1 (Ie): (690 V) 40 °C 50
(690 V) 60 °C 42 A
(690 V) 70 °C 37
Rated Operational Current AC-3 (Ie): (415 V) 60 °C 32 A
(440 V) 60 °C 32 A
(500 V) 60 °C 28 A
(690 V) 60 °C 21 A
(380 / 400 V) 60 °C 32 A
(220 / 230 / 240 V) 60 °C 33 A
Rated Operational Power AC-3 (Pe): (415 V) 15 kW
(440 V) 18.5 kW
(500 V) 18.5 kW
(690 V) 18.5 kW
(380 / 400 V) 15 kW
(220 / 230 / 240 V) 9 kW
Rated Short-time Withstand Current (Icw): at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 350 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 50 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 150 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 700 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 225 A
for 1 s -empty- A
Maximum Breaking Capacity: cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 500 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 200 A
Maximum Electrical Switching Frequency: (AC-1) 600 cycles per hour
(AC-15) 0 cycles per hour
(AC-2 / AC-4) 150 cycles per hour
(AC-3) 1200 cycles per hour
(DC-13) 0 cycles per hour
Rated Insulation Voltage (Ui): acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
acc. to IEC 60947-5-1 and VDE 0110 (Gr. C) 690 V
acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp): 6 kV
Maximum Mechanical Switching Frequency: 3600 cycles per hour
Rated Control Circuit Voltage (Uc): 50 Hz 24 V
60 Hz 24 V
Operate Time: Between Coil De-energization and NC Contact Closing 9 ... 20 ms
Between Coil De-energization and NO Contact Opening 4 ... 18 ms
Between Coil Energization and NC Contact Opening 7 ... 21 ms
Between Coil Energization and NO Contact Closing 10 ... 26 ms
Connecting Capacity Main Circuit: Flexible with Ferrule 1/2x 1 ... 6 mm²
Flexible with Insulated Ferrule 1/2x 1 ... 6 mm²
Flexible 1/2x 1 ... 6 mm²
Rigid 1/2x 1 ... 10 mm²
Connecting Capacity Auxiliary Circuit: Flexible 1/2x 1 ... 6 mm²
Rigid 1/2x 1 ... 2.5 mm²
Connecting Capacity Control Circuit: Flexible with Ferrule 1/2x 0.5 ... 2.5 mm²
Flexible with Insulated Ferrule 1/2x 0.5 ... 1.5 mm²
Flexible 1/2x 0.5 ... 2.5 mm²
Rigid 1/2x 1 ... 2.5 mm²
Wire Stripping Length: Control Circuit 10 mm
Main Circuit 14 mm
Degree of Protection: acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
Terminal Type: Push-in Spring Terminals
Technical UL/CSA
General Use Rating UL/CSA: (600 V AC) 45 A
Horsepower Rating UL/CSA: (120 V AC) Single Phase 2 hp
(200 ... 208 V AC) Three Phase 10 hp
(220 ... 240 V AC) Three Phase 10 hp
(240 V AC) Single Phase 5 hp
(440 ... 480 V AC) Three Phase 20 hp
(550 ... 600 V AC) Three Phase 25 hp

Environmental
Ambient Air Temperature: Close to Contactor Fitted with Thermal O/L Relay -25 ... +60 °C
Close to Contactor without Thermal O/L Relay -40 ... +70 °C
Close to Contactor for Storage -60 ... +80 °C
Near Contactor for Operation in Free Air -40 ... +70 °C
Climatic Withstand: Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible: 3000 m
Resistance to Vibrations acc. to IEC 60068-2-6: 5 ... 300 Hz 4 g closed position / 2 g open position

Certificates and Declarations (Document Number)
CB Certificate: CB_SE-96552M1
CQC Certificate: CQC2010010304445623
Declaration of Conformity - CCC: 2020980304001254
Declaration of Conformity - CE: 1SBD250024U1000
Instructions and Manuals: 1SBC101060M6801
RoHS Information: 1SBD251089E1000
UL Certificate: UL_20191021-E312527_7_1

Container Information
Package Level 1 Units: box 1 piece
Package Level 1 Width: 93 mm
Package Level 1 Depth / Length: 86 mm
Package Level 1 Height: 45 mm
Package Level 1 Gross Weight: 0.359 kg
Package Level 1 EAN: 3471523015005
Package Level 3 Units: 1080 piece

Classifications
Object Classification Code: Q
ETIM 6: EC000066 - Power contactor, AC switching
ETIM 7: EC000066 - Power contactor, AC switching
eClass: V11.0 : 27371003
UNSPSC: 39121529