Артикул: AFS205-30-12-12

Артикул: AFS205-30-12-12

AFS205-30-12-12
Мы подберем для вас подходящий продукт
sales@industry-analytics.ru
+7 (926) 540-72-98
Срочная доставка
Параллельный импорт

Конфигурация

















































General Information
Extended Product Type: AFS205-30-12-12
Product ID: 1SFL527082R1212
EAN: 7320500541531
Catalog Description: AFS205-30-12-12
Long Description: The AFS205-30-12-12 is a 3 pole - 1000 V IEC or 600 V UL contactor with pre-mounted 1 left (1 N.O + 1 N.C.) and fixed 1 right (1 N.C.) side mounted auxiliary contact blocks with Main Circuit Bars connections, controlling motors up to 110 kW / 400 V AC (AC-3) or 150 hp / 480 V UL and switching power circuits up to 350 A (AC-1) or 300 A UL general use. AFS contactors can be easily integrated in machine manufacturer’s systems complying with main standards EN ISO 13849 and EN 62061 - guaranteeing the safe use of your machinery and equipment. An easily identifiable yellow low energy auxiliary contact block ensures the status feedback circuits required in machine safety applications. Thanks to the AF technology, the contactor has a wide control voltage range (48-130 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.

Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85364900
Popular Downloads
Data Sheet, Technical Information: 1SBC100208C02__
Instructions and Manuals: 1SFC100008M0201

Dimensions
Product Net Width: 105 mm
Product Net Depth / Length: 152 mm
Product Net Height: 196 mm
Product Net Weight: 2.4 kg

Technical
Number of Main Contacts NO: 3
Number of Main Contacts NC: 0
Number of Auxiliary Contacts NO: 1
Number of Auxiliary Contacts NC: 2
Rated Operational Voltage: Main Circuit 1000 V
Rated Frequency (f): Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith): acc. to IEC 60947-4-1, Open Contactors q = 40 °C 350 A
Rated Operational Current AC-1 (Ie): (1000 V) 40 °C 275 A
(1000 V) 60 °C 250 A
(1000 V) 70 °C 200 A
(690 V) 40 °C 350
(690 V) 60 °C 300 A
(690 V) 70 °C 240
Rated Operational Current AC-3 (Ie): (415 V) 60 °C 205 A
(440 V) 60 °C 205 A
(500 V) 60 °C 165 A
(690 V) 60 °C 165 A
(1000 V) 60 °C 100 A
(380 / 400 V) 60 °C 205 A
(220 / 230 / 240 V) 60 °C 205 A
Rated Operational Power AC-3 (Pe): (415 V) 110 kW
(440 V) 132 kW
(500 V) 110 kW
(690 V) 160 kW
(1000 V) 132 kW
(380 / 400 V) 110 kW
(220 / 230 / 240 V) 55 kW
Rated Breaking Capacity AC-3 acc. to IEC 60947-4-1: 8 x Ie AC-3
Rated Making Capacity AC-3 acc. to IEC 60947-4-1: 10 x Ie AC-3
Short-Circuit Protective Devices: gG Type Fuses 400 A
Rated Short-time Withstand Current (Icw): at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1640 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 350 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 670 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 2050 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 947 A
Maximum Breaking Capacity: cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3500 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 2500 A
Maximum Electrical Switching Frequency: (AC-1) 300 cycles per hour
(AC-2 / AC-4) 150 cycles per hour
(AC-3) 300 cycles per hour
Rated Operational Current DC-1 (Ie): (110 V) 2 Poles in Series, 40 °C 275 A
(220 V) 3 Poles in Series, 40 °C 275 A
Rated Operational Current DC-3 (Ie): (110 V) 2 Poles in Series, 40 °C 275 A
(220 V) 3 Poles in Series, 40 °C 275 A
Rated Operational Current DC-5 (Ie): (110 V) 2 Poles in Series, 40 °C 275 A
(220 V) 3 Poles in Series, 40 °C 275 A
Rated Insulation Voltage (Ui): acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp): Main Circuit 8 kV
Mechanical Durability: 5 million
Maximum Mechanical Switching Frequency: 300 cycles per hour
Coil Operating Limits: (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Rated Control Circuit Voltage (Uc): 50 Hz 48 ... 130 V
60 Hz 48 ... 130 V
DC Operation 48 ... 130 V
Coil Consumption: Holding at Max. Rated Control Circuit Voltage 50 Hz 4 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 4 V·A
Holding at Max. Rated Control Circuit Voltage DC 2.5 W
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 175 V·A
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 175 V·A
Pull-in at Max. Rated Control Circuit Voltage DC 130 W
Operate Time: Between Coil De-energization and NO Contact Opening 37 ... 47 ms
Between Coil Energization and NO Contact Closing 25 ... 55 ms
Connecting Capacity Main Circuit: Flexible 2 x 50 ... 95 mm²
Rigid Al-Cable 1 x 95 ... 185 mm²
Rigid Cu-Cable 1 x 6 ... 150 mm²
Connecting Capacity Auxiliary Circuit: Flexible with Ferrule 1x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²
Flexible 2x0.75 ... 2.5 mm²
Solid 1 x 1 ... 4 mm²
Stranded 1 x 1 .... 4 mm²
Degree of Protection: acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Terminal Type: Main Circuit: Bars
Technical UL/CSA
Maximum Operating Voltage UL/CSA: Main Circuit 600 V
General Use Rating UL/CSA: (600 V AC) 300 A
Horsepower Rating UL/CSA: (200 ... 208 V AC) Three Phase 60 hp
(220 ... 240 V AC) Three Phase 75 hp
(440 ... 480 V AC) Three Phase 150 hp
(550 ... 600 V AC) Three Phase 200 hp

Environmental
Ambient Air Temperature: Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... +50 °C
Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... +70 °C
Close to Contactor for Storage -40 ... +70 °C
Maximum Operating Altitude Permissible: 3000 m
RoHS Status: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

Certificates and Declarations (Document Number)
CB Certificate: SE-82315
CQC Certificate: CQC2014010304676685
cUL Certificate: 20121023-E36588
Declaration of Conformity - CCC: 2020980304001306
Declaration of Conformity - CE: 2CMT2018-005695
EAC Certificate: 1SFC101360D1101
Instructions and Manuals: 1SFC100008M0201
RoHS Information: 2CMT2018-005695
SUVA Certificate: 2CMT2019-005857

Container Information
Package Level 1 Units: box 1 piece
Package Level 1 Width: 160 mm
Package Level 1 Depth / Length: 258 mm
Package Level 1 Height: 235 mm
Package Level 1 Gross Weight: 3 kg
Package Level 1 EAN: 7320500541531

Classifications
Object Classification Code: Q
ETIM 4: EC000066 - Magnet contactor, AC-switching
ETIM 5: EC000066 - Magnet contactor, AC-switching
ETIM 6: EC000066 - Power contactor, AC switching
ETIM 7: EC000066 - Power contactor, AC switching
eClass: V11.0 : 27371003
UNSPSC: 39121529
IDEA Granular Category Code (IGCC): 4755 >> Contactors
E-Number (Finland): 3709011