Артикул: AF305-30-11-13
Мы подберем для вас подходящий продукт
Срочная доставка
Параллельный импорт
Конфигурация
General Information | |
Extended Product Type: | AF305-30-11-13 |
Product ID: | 1SFL587002R1311 |
EAN: | 7320500481776 |
Catalog Description: | AF305-30-11-13 Contactor |
Long Description: | The AF305-30-11-13 is a 3 pole - 1000 V IEC or 600 V UL contactor with pre-mounted auxiliary contacts and Main Circuit Bars, controlling motors up to 160 kW / 400 V AC (AC-3) or 250 hp / 480 V UL and switching power circuits up to 500 A (AC-1) or 400 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories. |
| |
Minimum Order Quantity: | 1 piece |
Customs Tariff Number: | 85364900 |
Popular Downloads | |
Data Sheet, Technical Information: | 1SBC100192C0206 |
Instructions and Manuals: | 1SFC100008M0201 |
Dimension Diagram: | 1SFB535001G1060 |
| |
Product Net Width: | 140 mm |
Product Net Depth / Length: | 180 mm |
Product Net Height: | 225 mm |
Product Net Weight: | 3.9 kg |
| |
Number of Main Contacts NO: | 3 |
Number of Main Contacts NC: | 0 |
Number of Auxiliary Contacts NO: | 1 |
Number of Auxiliary Contacts NC: | 1 |
Rated Operational Voltage: | Main Circuit 1000 V |
Rated Frequency (f): | Main Circuit 50 / 60 Hz |
Conventional Free-air Thermal Current (Ith): | acc. to IEC 60947-4-1, Open Contactors q = 40 °C 500 A |
Rated Operational Current AC-1 (Ie): | (1000 V) 40 °C 375 A |
(1000 V) 55 °C 325 A | |
(1000 V) 60 °C 325 A | |
(1000 V) 70 °C 260 A | |
(690 V) 40 °C 500 | |
(690 V) 55 °C 400 | |
(690 V) 70 °C 325 | |
Rated Operational Current AC-3 (Ie): | (415 V) 55 °C 305 A |
(440 V) 55 °C 305 A | |
(500 V) 55 °C 290 A | |
(690 V) 55 °C 290 A | |
(1000 V) 55 °C 131 A | |
(380 / 400 V) 55 °C 305 A | |
(220 / 230 / 240 V) 55 °C 305 | |
Rated Operational Power AC-3 (Pe): | (415 V) 160 kW |
(440 V) 160 kW | |
(500 V) 200 kW | |
(690 V) 250 kW | |
(1000 V) 185 kW | |
(380 / 400 V) 160 kW | |
(220 / 230 / 240 V) 90 kW | |
Rated Breaking Capacity AC-3 acc. to IEC 60947-4-1: | 8 x Ie AC-3 |
Rated Making Capacity AC-3 acc. to IEC 60947-4-1: | 10 x Ie AC-3 |
Short-Circuit Protective Devices: | gG Type Fuses 500 A |
Rated Short-time Withstand Current (Icw): | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 2440 A |
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 500 A | |
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 996 A | |
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 3050 A | |
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 1409 A | |
Maximum Breaking Capacity: | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 4600 A |
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 3800 A | |
Maximum Electrical Switching Frequency: | (AC-1) 300 cycles per hour |
(AC-2 / AC-4) 150 cycles per hour | |
(AC-3) 300 cycles per hour | |
Rated Operational Current DC-1 (Ie): | (110 V) 1-Pole, 40 °C 500 A |
(220 V) 2 Poles in Series, 40 °C 500 A | |
(220 V) 3 Poles in Series, 40 °C 500 A | |
Rated Operational Current DC-3 (Ie): | (110 V) 2 Poles in Series, 40 °C 400 A |
(220 V) 3 Poles in Series, 40 °C 400 A | |
Rated Operational Current DC-5 (Ie): | (110 V) 2 Poles in Series, 40 °C 400 A |
(220 V) 3 Poles in Series, 40 °C 400 A | |
Rated Insulation Voltage (Ui): | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V |
acc. to UL/CSA 600 V | |
Rated Impulse Withstand Voltage (Uimp): | Main Circuit 8 kV |
Mechanical Durability: | 5 million |
Maximum Mechanical Switching Frequency: | 300 cycles per hour |
Coil Operating Limits: | (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C) |
Rated Control Circuit Voltage (Uc): | 50 Hz 100 ... 250 V |
60 Hz 100 ... 250 V | |
DC Operation 100 ... 250 V | |
Coil Consumption: | Holding at Max. Rated Control Circuit Voltage 50 Hz 17.5 V·A |
Holding at Max. Rated Control Circuit Voltage 60 Hz 17.5 V·A | |
Holding at Max. Rated Control Circuit Voltage DC 4.5 W | |
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 385 V·A | |
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 385 V·A | |
Pull-in at Max. Rated Control Circuit Voltage DC 410 W | |
Operate Time: | Between Coil De-energization and NO Contact Opening 37 ... 47 ms |
Between Coil Energization and NO Contact Closing 25 ... 55 ms | |
Connecting Capacity Main Circuit: | Flexible 1 x 16 ... 240 mm² |
Rigid Al-Cable 1 x 185 ... 240 mm² | |
Rigid Cu-Cable 2 x 70 ... 185 mm² | |
Connecting Capacity Auxiliary Circuit: | Flexible with Ferrule 1x 0.75 ... 2.5 mm² |
Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm² | |
Flexible 1x0.75 ... 2.5 mm² | |
Solid 2 x 1 ... 4 mm² | |
Stranded 1 x 1 .... 4 mm² | |
Degree of Protection: | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 |
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00 | |
Terminal Type: | Main Circuit: Bars |
Technical UL/CSA | |
Maximum Operating Voltage UL/CSA: | Main Circuit 1000 V |
General Use Rating UL/CSA: | (600 V AC) 400 A |
Horsepower Rating UL/CSA: | (200 V AC) Three Phase 100 hp |
(208 V AC) Three Phase 100 hp | |
(220 ... 240 V AC) Three Phase 125 hp | |
(440 ... 480 V AC) Three Phase 250 hp | |
(550 ... 600 V AC) Three Phase 300 hp | |
| |
Ambient Air Temperature: | Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... +50 °C |
Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... +70 °C | |
Close to Contactor for Storage -40 ... +70 °C | |
Maximum Operating Altitude Permissible: | 3000 m |
RoHS Status: | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| |
ABS Certificate: | 14-LD1092198-PDA |
BV Certificate: | BV_36353_A0BV |
CB Certificate: | SE-89316 |
CCS Certificate: | GB14T00030 |
CQC Certificate: | CQC2014010304676670 |
CQC2014010304673866 | |
cUL Certificate: | 20121217-E36588 |
Declaration of Conformity - CCC: | 2020980304001305 |
2020980304001068 | |
Declaration of Conformity - CE: | 2CMT2015-005439 |
DNV Certificate: | DNV_E-14043 |
DNV GL Certificate: | DNV_E-14043 |
EAC Certificate: | 9AKK107046A8618 |
Environmental Information: | 2CMT004732 |
1SAC200043H0005 | |
GL Certificate: | GL_95073-14HH |
Instructions and Manuals: | 1SFC100008M0201 |
LR Certificate: | LR_14_70011(E1) |
PRS Certificate: | TE_2092_880423_16 |
RINA Certificate: | ELE060313XG_002 |
RMRS Certificate: | 9AKK107045A6978 |
RoHS Information: | 2CMT2015-005439 |
UL Listing Card: | UL_E36588 |
| |
Package Level 1 Units: | box 1 piece |
Package Level 1 Width: | 263 mm |
Package Level 1 Depth / Length: | 203 mm |
Package Level 1 Height: | 289 mm |
Package Level 1 Gross Weight: | 4.6 kg |
Package Level 1 EAN: | 7320500481776 |
| |
Object Classification Code: | Q |
ETIM 4: | EC000066 - Magnet contactor, AC-switching |
ETIM 5: | EC000066 - Magnet contactor, AC-switching |
ETIM 6: | EC000066 - Power contactor, AC switching |
ETIM 7: | EC000066 - Power contactor, AC switching |
eClass: | V11.0 : 27371003 |
UNSPSC: | 39121529 |
IDEA Granular Category Code (IGCC): | 4755 >> Contactors |
E-Number (Finland): | 3706486 |
E-Number (Norway): | 4117650 |
E-Number (Sweden): | 3210163 |