Артикул: A210-30-22-81

Артикул: A210-30-22-81

A210-30-22 24V 50Hz / 24V 60Hz Contactor
ΠœΡ‹ ΠΏΠΎΠ΄Π±Π΅Ρ€Π΅ΠΌ для вас подходящий ΠΏΡ€ΠΎΠ΄ΡƒΠΊΡ‚
sales@industry-analytics.ru
+7 (926) 540-72-98
Брочная доставка
ΠŸΠ°Ρ€Π°Π»Π»Π΅Π»ΡŒΠ½Ρ‹ΠΉ ΠΈΠΌΠΏΠΎΡ€Ρ‚

ΠšΠΎΠ½Ρ„ΠΈΠ³ΡƒΡ€Π°Ρ†ΠΈΡ

















































General Information
Extended Product Type: A210-30-22-81
Product ID: 1SFL511001R8122
EAN: 7320500212905
Catalog Description: A210-30-22 24V 50Hz / 24V 60Hz Contactor
Long Description: A 3-phase Contactor suitable for various applications such as Motor starting, Isolation, By-pass and Distribution application up to max 690 V.Operated with control voltage, versions from 24….690 AC, 50 and 60 Hz

Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85364900
Replacement Product ID (NEW): 1SFL527002R1122
Popular Downloads
Data Sheet, Technical Information: 1SBC100192C0206
Instructions and Manuals: 1SFC380003-89
Dimension Diagram: 53540930-2

Dimensions
Product Net Width: 140 mm
Product Net Depth / Length: 180.5 mm
Product Net Height: 227 mm
Product Net Weight: 5.4 kg

Technical
Number of Main Contacts NO: 3
Number of Main Contacts NC: 0
Number of Auxiliary Contacts NO: 2
Number of Auxiliary Contacts NC: 2
Rated Operational Voltage: Main Circuit 690 V
Rated Frequency (f): Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith): acc. to IEC 60947-4-1, Open Contactors q = 40 Β°C 350 A
Rated Operational Current AC-1 (Ie): (690 V) 40 Β°C 350
(690 V) 55 Β°C 300
(690 V) 70 Β°C 240
Rated Operational Current AC-3 (Ie): (415 V) 55 Β°C 210 A
(440 V) 55 Β°C 210 A
(500 V) 55 Β°C 210 A
(690 V) 55 Β°C 210 A
(380 / 400 V) 55 Β°C 210 A
(220 / 230 / 240 V) 55 Β°C 210
Rated Operational Power AC-3 (Pe): (415 V) 110 kW
(440 V) 110 kW
(500 V) 132 kW
(690 V) 160 kW
(380 / 400 V) 110 kW
(220 / 230 / 240 V) 59 kW
Rated Breaking Capacity AC-3 acc. to IEC 60947-4-1: 8 x Ie AC-3
Rated Making Capacity AC-3 acc. to IEC 60947-4-1: 10 x Ie AC-3
Short-Circuit Protective Devices: gG Type Fuses 400 A
Rated Short-time Withstand Current (Icw): at 40 Β°C Ambient Temp, in Free Air, from a Cold State 10 s 1700 A
at 40 Β°C Ambient Temp, in Free Air, from a Cold State 15 min 400 A
at 40 Β°C Ambient Temp, in Free Air, from a Cold State 1 min 1000 A
at 40 Β°C Ambient Temp, in Free Air, from a Cold State 1 s 2500 A
at 40 Β°C Ambient Temp, in Free Air, from a Cold State 30 s 1200 A
Maximum Breaking Capacity: cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 2200 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 2000 A
Maximum Electrical Switching Frequency: (AC-1) 300 cycles per hour
(AC-2 / AC-4) 150 cycles per hour
(AC-3) 300 cycles per hour
Rated Operational Current DC-1 (Ie): (110 V) 2 Poles in Series, 40 Β°C 350 A
(220 V) 3 Poles in Series, 40 Β°C 350 A
Rated Operational Current DC-3 (Ie): (110 V) 2 Poles in Series, 40 Β°C 350 A
(220 V) 3 Poles in Series, 40 Β°C 350 A
Rated Operational Current DC-5 (Ie): (110 V) 2 Poles in Series, 40 Β°C 350 A
(220 V) 3 Poles in Series, 40 Β°C 350 A
Rated Insulation Voltage (Ui): acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp): Main Circuit 8 kV
Mechanical Durability: 5 million
Maximum Mechanical Switching Frequency: 3600 cycles per hour
Coil Operating Limits: (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at ΞΈ ≀ 70 Β°C)
Rated Control Circuit Voltage (Uc): 50 Hz 24 V
60 Hz 24 V
Coil Consumption: Holding at Max. Rated Control Circuit Voltage 50 Hz 60 VΒ·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 65 VΒ·A
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 1350 VΒ·A
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 1550 VΒ·A
Operate Time: Between Coil De-energization and NC Contact Closing 7 ... 13 ms
Between Coil De-energization and NO Contact Opening 10 ... 16 ms
Between Coil Energization and NC Contact Opening 12 ... 30 ms
Between Coil Energization and NO Contact Closing 17 ... 35 ms
Connecting Capacity Main Circuit: Bar 32 mmΒ²
Rigid Al-Cable 120 ... 240 mmΒ²
Rigid Cu-Cable 16 ... 240 mmΒ²
Connecting Capacity Auxiliary Circuit: Flexible with Ferrule 2x 0.75 ... 2.5 mmΒ²
Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mmΒ²
Flexible 1x0.75 ... 2.5 mmΒ²
Solid 2 x 1 ... 4 mmΒ²
Stranded 2 x 1 .... 4 mmΒ²
Degree of Protection: acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Connecting Terminals (delivered in open position) Main Poles: Flat type c/w screws and bolts
Terminal Type: Main Circuit: Bars
Technical UL/CSA
Maximum Operating Voltage UL/CSA: Main Circuit 600 V
General Use Rating UL/CSA: (600 V AC) 300 A
Horsepower Rating UL/CSA: (200 V AC) Three Phase 60 hp
(208 V AC) Three Phase 60 hp
(220 ... 240 V AC) Three Phase 75 hp
(440 ... 480 V AC) Three Phase 150 hp
(550 ... 600 V AC) Three Phase 200 hp

Environmental
Ambient Air Temperature: Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... +50 Β°C
Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... +70 Β°C
Close to Contactor for Storage -40 ... +70 Β°C
Maximum Operating Altitude Permissible: 3000 m
Resistance to Shock acc. to IEC 60068-2-27: Shock Direction: A 5 K40
Shock Direction: B1 5 K40
Shock Direction: B2 5 K40
Shock Direction: C1 5 K40
Shock Direction: C2 5 K40
RoHS Status: Following EU Directive 2011/65/EU

Certificates and Declarations (Document Number)
BV Certificate: 09826/C0 BV
CQC Certificate: CQC2008010304279325
Declaration of Conformity - CCC: 2020980304001552
Declaration of Conformity - CE: 2CMT2015-005436
DNV Certificate: DNV_E-12191
Environmental Information: 1SFC101003D0201
GL Certificate: GL_15529-00HH
Instructions and Manuals: 1SFC380003-89
LOVAG Certificate: IT00051
LR Certificate: LR_12-70003
RINA Certificate: ELE060313XG/001
RMRS Certificate: RMRS_12-03683-315
RoHS Information: 2CMT2015-005436

Container Information
Package Level 1 Units: box 1 piece
Package Level 1 Width: 203 mm
Package Level 1 Depth / Length: 245 mm
Package Level 1 Height: 188 mm
Package Level 1 Gross Weight: 6.1 kg
Package Level 1 EAN: 7320500212905

Classifications
Object Classification Code: Q
ETIM 4: EC000066 - Magnet contactor, AC-switching
ETIM 5: EC000066 - Magnet contactor, AC-switching
ETIM 6: EC000066 - Power contactor, AC switching
ETIM 7: EC000066 - Power contactor, AC switching
eClass: V11.0 : 27371003
UNSPSC: 39121529
IDEA Granular Category Code (IGCC): 4755 >> Contactors