General Information
Extended Product Type: A26-40-00 110-115V 50Hz / 115-127V 60Hz
Product ID: 1SBL241201R8900
EAN: 3471522063892
Catalog Description: A26-40-00 110-115V 50Hz / 115-127V 60Hz Contactor
Long Description: A26 4-pole contactors are mainly used for controlling non-inductive or slightly inductive loads (i.e. resistance furnaces...) and generally for controlling power circuits up to 690 V AC and 440 V DC. The contactors can also be used for many other applications such lighting... The A... series 4-pole contactors are of the block type design. - Main poles and auxiliary contact blocks: 4 N.O. main poles, front and side-mounted add-on auxiliary contact blocks - Control circuit: AC operated with laminated magnet circuit - Accessories: a wide range of accessories is available.

Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85364900
Popular Downloads
Data Sheet, Technical Information: 1SBC100122C0202_Ch02
Instructions and Manuals: FPTC407722P0001

Dimensions
Product Net Width: 54 mm
Product Net Depth / Length: 93.6 mm
Product Net Height: 90 mm
Product Net Weight: 0.61 kg

Technical
Number of Main Contacts NO: 4
Number of Main Contacts NC: 0
Number of Auxiliary Contacts NO: 0
Number of Auxiliary Contacts NC: 0
Standards: Devices complying with international standards IEC 947-1 / 947-4-1, and European standards EN 60 947-1 / 60 947-4-1. Electromagnetic compatibility (EMC) acc. to amendment A11 to IEC 947-1, EN 60 947-1 and amendment 2 to IEC 947-4-1
Rated Operational Voltage: Main Circuit 690 V
Conventional Free-air Thermal Current (Ith): acc. to IEC 60947-4-1, Open Contactors q = 40 °C 45 A
Rated Operational Current AC-1 (Ie): (690 V) 40 °C 45
(690 V) 55 °C 40
(690 V) 70 °C 32
Rated Operational Current AC-3 (Ie): (415 V) 55 °C 26 A
(440 V) 55 °C 26 A
(500 V) 55 °C 22 A
(690 V) 55 °C 17 A
(380 / 400 V) 55 °C 26 A
(220 / 230 / 240 V) 55 °C 26
Rated Operational Power AC-3 (Pe): (415 V) 15 kW
(440 V) 15 kW
(500 V) 15 kW
(380 / 400 V) 11 kW
(220 / 230 / 240 V) 6.5 kW
Rated Breaking Capacity AC-3 acc. to IEC 60947-4-1: 8 x Ie AC-3
Rated Making Capacity AC-3 acc. to IEC 60947-4-1: 10 x Ie AC-3
Short-Circuit Protective Devices: gG Type Fuses 50 A
Maximum Breaking Capacity: cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 420 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 170 A
Maximum Electrical Switching Frequency: (AC-1) 600 cycles per hour
(AC-2 / AC-4) 300 cycles per hour
(AC-3) 1200 cycles per hour
Rated Insulation Voltage (Ui): acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp): 8 kV
Mechanical Durability: 10 million
Maximum Mechanical Switching Frequency: 3600 cycles per hour
Rated Control Circuit Voltage (Uc): 50 Hz 110 ... 115 V
60 Hz 115 ... 127 V
Coil Consumption: Average Holding Value 50 / 60 Hz 12 V·A
Average Pull-in Value 50 Hz 125 V·A
Average Pull-in Value 60 Hz 120 V·A
Holding at Max. Rated Control Circuit Voltage 50 Hz 12 3 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 12 3 V·A
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 120 V·A
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 140 V·A
Operate Time: Between Coil De-energization and NO Contact Opening 4 ... 11 ms
Between Coil Energization and NO Contact Closing 8 ... 21 ms
Connecting Capacity Main Circuit: Flexible with Cable End 0.75 ... 4 mm²
Rigid Cable 1.5 ... 6 mm²
Connecting Capacity Auxiliary Circuit: Flexible with Cable End 0.75 ... 2.5 mm²
Rigid Cable 1 ... 4 mm²
Degree of Protection: acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
Connecting Terminals (delivered in open position) Main Poles: M 4 (+,-) pozidriv 2 screws with cable clamp
Terminal Type: Screw Terminals

Environmental
Ambient Air Temperature: Close to Contactor for Storage -60 ... +80 °C
Near Contactor for Operation in Free Air (0.85 ... 1.1 Uc) -40 ... +55 °C
Near Contactor for Operation in Free Air (Uc) -40 ... +70 °C
Climatic Withstand: acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II
Maximum Operating Altitude Permissible: 3000 m
Resistance to Shock acc. to IEC 60068-2-27: Closed, Shock Direction: B1 10 K40
Open, Shock Direction: B1 5 K40
Shock Direction: A 20 K40
Shock Direction: B2 15 K40
Shock Direction: C1 20 K40
Shock Direction: C2 20 K40
RoHS Status: Following EU Directive 2011/65/EU

Certificates and Declarations (Document Number)
BV Certificate: BV_2634H07559E0
CCC Certificate: CCC_2013010304615752
CQC Certificate: CQC2013010304615752
CQC2004010309133982
CSA Certificate: CSA_1033838_LR056745
Declaration of Conformity - CCC: 2020980304001609
2020980304001227
Declaration of Conformity - CE: 1SBD250802U1000
DNV Certificate: DNV-GL_TAE00000TX
DNV GL Certificate: DNV-GL_TAE00000TX
EAC Certificate: EAC_RU C-FR ME77 B03599
Environmental Information: 1SBD250004E1003
Instructions and Manuals: FPTC407722P0001
LOVAG Certificate: LOVAG_FR97083
LR Certificate: LRS_9830011E4
RINA Certificate: RINA_ELE172319XG001
RMRS Certificate: RMRS_0507015250
RoHS Information: 1SBD250802U1000
UL Certificate: UL_071301E39231

Container Information
Package Level 1 Units: 1 piece
Package Level 1 Width: 101 mm
Package Level 1 Depth / Length: 115 mm
Package Level 1 Height: 61 mm
Package Level 1 Gross Weight: 0.61 kg
Package Level 1 EAN: 3471522063892
Package Level 2 Units: box 24 piece
Package Level 2 Width: 300 mm
Package Level 2 Depth / Length: 245 mm
Package Level 2 Height: 308 mm
Package Level 2 Gross Weight: 14.64 kg
Package Level 3 Units: 576 piece

Classifications
Object Classification Code: Q
ETIM 4: EC000066 - Magnet contactor, AC-switching
ETIM 5: EC000066 - Magnet contactor, AC-switching
ETIM 6: EC000066 - Power contactor, AC switching
ETIM 7: EC000066 - Power contactor, AC switching
eClass: V11.0 : 27371003
UNSPSC: 39121529