Артикул: AF190-30-22-34

Артикул: AF190-30-22-34

AF190-30-22-34 Contactor
ΠœΡ‹ ΠΏΠΎΠ΄Π±Π΅Ρ€Π΅ΠΌ для вас подходящий ΠΏΡ€ΠΎΠ΄ΡƒΠΊΡ‚
sales@industry-analytics.ru
+7 (926) 540-72-98
Брочная доставка
ΠŸΠ°Ρ€Π°Π»Π»Π΅Π»ΡŒΠ½Ρ‹ΠΉ ΠΈΠΌΠΏΠΎΡ€Ρ‚

ΠšΠΎΠ½Ρ„ΠΈΠ³ΡƒΡ€Π°Ρ†ΠΈΡ







































General Information
Extended Product Type: AF190-30-22-34
Product ID: 1SFL487002R3422
EAN: 7320500480724
Catalog Description: AF190-30-22-34 Contactor
Long Description: The AF190-30-22-34 is a 3 pole - 1000 V IEC or 600 V UL contactor with pre-mounted auxiliary contacts and Main Circuit Bars, controlling motors up to 90 kW / 400 V AC (AC-3) or 125 hp / 480 V UL and switching power circuits up to 275 A (AC-1) or 250 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (250-500 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.

Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85364900
Popular Downloads
Data Sheet, Technical Information: 1SBC100192C02
Instructions and Manuals: 1SFC100008M0201

Dimensions
Product Net Width: 105 mm
Product Net Depth / Length: 169.5 mm
Product Net Height: 196 mm
Product Net Weight: 2.4 kg

Technical
Number of Main Contacts NO: 3
Number of Main Contacts NC: 0
Number of Auxiliary Contacts NO: 2
Number of Auxiliary Contacts NC: 2
Rated Operational Voltage: Main Circuit 1000 V
Rated Frequency (f): Main Circuit 60 Hz
Conventional Free-air Thermal Current (Ith): acc. to IEC 60947-4-1, Open Contactors q = 40 Β°C 275 A
Rated Operational Current AC-1 (Ie): (1000 V) 40 Β°C 250 A
(1000 V) 55 Β°C 225 A
(1000 V) 60 Β°C 225 A
(1000 V) 70 Β°C 185 A
(690 V) 40 Β°C 275
(690 V) 55 Β°C 250
(690 V) 60 Β°C 250 A
(690 V) 70 Β°C 200
Rated Operational Current AC-3 (Ie): (415 V) 55 Β°C 190 A
(440 V) 55 Β°C 190 A
(500 V) 55 Β°C 156 A
(690 V) 55 Β°C 135 A
(1000 V) 55 Β°C 85 A
(380 / 400 V) 55 Β°C 190 A
(220 / 230 / 240 V) 55 Β°C 190
Rated Operational Power AC-3 (Pe): (415 V) 90 kW
(440 V) 110 kW
(500 V) 110 kW
(690 V) 132 kW
(1000 V) 110 kW
(380 / 400 V) 90 kW
(220 / 230 / 240 V) 55 kW
Rated Breaking Capacity AC-3 acc. to IEC 60947-4-1: 8 x Ie AC-3
Rated Making Capacity AC-3 acc. to IEC 60947-4-1: 10 x Ie AC-3
Short-Circuit Protective Devices: gG Type Fuses 355 A
Rated Short-time Withstand Current (Icw): at 40 Β°C Ambient Temp, in Free Air, from a Cold State 10 s 1520 A
at 40 Β°C Ambient Temp, in Free Air, from a Cold State 15 min 275 A
at 40 Β°C Ambient Temp, in Free Air, from a Cold State 1 min 621 A
at 40 Β°C Ambient Temp, in Free Air, from a Cold State 1 s 1900 A
at 40 Β°C Ambient Temp, in Free Air, from a Cold State 30 s 878 A
Maximum Electrical Switching Frequency: (AC-1) 300 cycles per hour
(AC-2 / AC-4) 150 cycles per hour
(AC-3) 300 cycles per hour
Rated Insulation Voltage (Ui): acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp): 8 kV
Mechanical Durability: 5 million
Maximum Mechanical Switching Frequency: 300 cycles per hour
Coil Operating Limits: (acc. to IEC 60947-4-1) Uc (at ΞΈ ≀ 70 Β°C)
Rated Control Circuit Voltage (Uc): 50 Hz 250 ... 500 V
60 Hz 250 ... 500 V
DC Operation 250 ... 500 V
Coil Consumption: Holding at Max. Rated Control Circuit Voltage 50 Hz 16.1 VΒ·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 16.1 VΒ·A
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 185 VΒ·A
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 185 VΒ·A
Pull-in at Max. Rated Control Circuit Voltage DC 188 W
Operate Time: Between Coil De-energization and NO Contact Opening 37 ... 47 ms
Between Coil Energization and NO Contact Closing 25 ... 55 ms
Degree of Protection: acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP40
Terminal Type: Main Circuit: Bars
Technical UL/CSA
Maximum Operating Voltage UL/CSA: Main Circuit 1000 V

Environmental
Ambient Air Temperature: Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... +55 Β°C
Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... +70 Β°C
Close to Contactor for Storage -40 ... +70 Β°C
Maximum Operating Altitude Permissible: 3000 m
RoHS Status: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

Certificates and Declarations (Document Number)
ABS Certificate: 14-LD1092198-PDA
BV Certificate: BV_36353_A0BV
CB Certificate: SE-82315
CCS Certificate: GB14T00030
CQC Certificate: CQC2014010304676685
CQC2014010304724672
cUL Certificate: 20121023-E36588
Declaration of Conformity - CCC: 2020980304001306
2020980304001071
Declaration of Conformity - CE: 2CMT2015-005439
DNV Certificate: DNV_E-14043
DNV GL Certificate: DNV_E-14043
EAC Certificate: 9AKK107046A8618
Environmental Information: 2CMT004732
1SAC200042H0004
GL Certificate: GL_95072-14HH
Instructions and Manuals: 1SFC100008M0201
KC Certificate: 9AKK107046A9912
LR Certificate: LR_14_70011(E1)
PRS Certificate: TE_2092_880423_16
RINA Certificate: ELE060313XG_002
RMRS Certificate: 9AKK107045A6978
RoHS Information: 2CMT2015-005439
UL Listing Card: UL_E36588

Container Information
Package Level 1 Units: box 1 piece
Package Level 1 Width: 160 mm
Package Level 1 Depth / Length: 258 mm
Package Level 1 Height: 235 mm
Package Level 1 Gross Weight: 3 kg
Package Level 1 EAN: 7320500480724

Classifications
Object Classification Code: Q
ETIM 4: EC000066 - Magnet contactor, AC-switching
ETIM 5: EC000066 - Magnet contactor, AC-switching
ETIM 6: EC000066 - Power contactor, AC switching
ETIM 7: EC000066 - Power contactor, AC switching
eClass: V11.0 : 27371003
UNSPSC: 39121529
IDEA Granular Category Code (IGCC): 4755 >> Contactors
E-Number (Finland): 3707502